AVEVA™ System Platform 2023 R2 Patch 01 Readme

This patch release includes the following changes:

  • Incorporation of hot fixes for all products
  • Miscellaneous bug fixes
  • Improvements to the OMI web client. See the Application Server and AVEVA OMI 2023 R2 Patch 01 Readme for more information.

Supported System Platform Versions for Product Upgrade

This patch can only be applied to System Platform 2023 R2.

Important! System Platform does not support mixed Windows workgroup/domain environments. As stated in the System Platform 2023 R2 Installation Guide, although workgroups are supported, domain-based networking is recommended. However, you cannot use workgroup nodes within a domain environment.

Readme Files for Other Products in this Release

The extracted patch files include a ReadMe directory with the Readme files for each individual component product. To access the product Readme files, navigate to the applicable folder under the ReadMe directory. Review the known and resolved issues contained in each file as applicable.

Resolved issues — 2023 R2 Patch 01

See the product-specific ReadMe files (in the ReadMe directory, as described above) for issues resolved in this patch release. The table below shows issues resolved in components that are shared between two or more products and issues that were resolved too late to be included in the Readme file for their product.

Original Issue

Case/SR Number

Description

IMS 3199110

960396336

In the Industrial Graphic Editor, trying to create a script by selecting Scripts (Collection) from the Properties tab did not work. You could not type anything in the body of the script and warning messages were written to the logger.

IMS 3022955

960377542

After migrating a galaxy from System Platform 2023 Patch 03 to 2023R2, some graphics that were attached to object templates could not be opened in the Industrial Graphic Editor. Trying to open the graphic caused the message Graphic Not Available.

IMS 3034154

960374098

In InTouch, signing in using a smart card for authentication took approximately one minute. While the issue occurred in InTouch, the fix for it is in Application Server.

InTouch HMI Resolved Issues and Known Issues

InTouch HMI Resolved Issues

In addition to the fixes listed in the InTouch HMI 2023 R2 P01 Readme file, InTouch includes fixes for the issues listed in the following table. These issues were fixed too late to be included in the InTouch Readme.

Original Issue

Case/SR Number

Description

IMS-3054559

960384212

InTouch HMI was logging null values to Historian for the tags that had initialization value set to 0.

IMS-3058936

960380845

In InTouch HMI runtime, when multimonitor screen was used, the maximize option did not cover the complete resolution of the screens.

IMS-3183859

960392314

The Galaxy Browser window did not show all properties for Trend Client Control and Show all properties checkbox was disabled.

IMS-3280020

960402885

WindowMaker printout had an unusual background if  Images/Graphics were selected as HTML file.

IMS-3287663

960409213

There was a handle leak on Alarm Client Control when the RunQuery() method was called.

IMS-3292969

960406554

Post-upgrade from InTouch HMI 2020 R2 P01 to InTouch HMI 2023 R2, the Web widget could not be opened in the Azure Power Application.

IMS-3302540

960412777

Status element in Industraial Graphic did not expose properties in scripts which resulted in warnings. Also, could not add a ‘dot’ after the status element name in a script.

IMS-3303422

960407542

The SQLSelect() function did not work if a string was used with the WhereExpr parameter.

IMS-3307715

960414467

On a Chinese install of InTouch HMI, the help file of Industrial Graphic Editor was in German language instead of Chinese.

IMS-3337421

960420385

When tried to zoom-out an Industrial Graphic symbol or set to fit to window, the graphic changed to red-X and it could not be recovered later.

IMS-3341495

960413176

Post-upgrade from InTouch HMI 2017 U3 SP1 to InTouch HMI 2023 R2, there were issues navigating to some of the windows.

InTouch HMI Known Issues

The following are the known issues that remain in the release of InTouch HMI 2023 R2 P01.

Issue ID

Description

3298289

Insight screen showed blank when tried to publish data from InTouch HMI.

Workaround:

  1. Go to C:\Program Files (x86)\Wonderware\Intouch\InsightPublisher\x64 and open the aahCloudConfigurator.exe.config file.
  2. Update the following values:
    • <add key=”PublisherProcess” value=”C:\Program Files (x86)\Wonderware\InTouch\InsightPublisher\x64\aahInTouchTagImport.exe” />
    • <add key=”PublisherPrerequisite” value=”C:\Program Files (x86)\Wonderware\InTouch\InsightPublisher\x64\aahPublisherPrerequisites.dll” />
  3. Relaunch the publisher.

Documentation corrections

This section lists pending corrections to System Platform documentation. These changes will appear in the next product release.

In the System Platform Installation Guide

Location

Existing Text

Change

System Platform Installation Guide
(System Platform 2023 R2)

Modifying an Installation (page 133)

Step 6

Click Finish.

Note: The system may not prompt you to restart the system after Modify is successful. However, if you have added a new product or feature, a system restart is recommended.

Add step 7 after the note.

Step 7
After the modify operation has finished and you have rebooted the system, re-install any patches or hotfixes that were previously installed. This ensures that the new components are patched to the same level as the previously installed components.

If the patch installation informs you that the patch is already installed, continue with the installation anyway. There is no harm in installing a patch a second time.

System Platform Installation Guide
(System Platform 2023 R2)

Repairing an Installation (page 135)

Step 7

When the update has finished, the Process Complete dialog box appears. Click Finish to close the dialog box and complete the process.

Add step 8.

The repair process may overwrite patched files with unpatched earlier versions of the files. After the repair process has finished, re-install any patches or hotfixes that were previously installed.

If the patch installation informs you that the patch is already installed, continue with the installation anyway. There is no harm in installing a patch a second time.